| General | |
| Topology | On-line double conversion with automatic by-pass and power factor correction |
| Configuration | Rack/Tower |
| Part Number | M68401 |
| Color | metallic grey |
| Rating (VA/Watts) | 2200/1980 |
| Dimensions (H x W x D, mm) | 440 x 86 x 640 |
| Weight (kg) | 30 |
| Warranty | 2 years warranty, Standard product exchange, including the battery |
| Rail Kit Included | Yes |
| Electrical Input | |
| Connection | IEC-320-C20 |
| Input Voltage Without Using Batteries | 100/120/160/184 V to 284V Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively |
| Input frequency Range Without Using Batteries | 40 to 70 Hz |
| Electrical Output | |
| Voltages | 230 V (adjustable to 200/208/220/240 V) |
| Output Receptacles | (8) IEC-320-C13, (1) IEC-320-C19 |
| Remotely controlled sockets | 2 groups of 2 x IEC C13 (10A) on EX |
| Output Frequency | 50/60 Hz auto-select or frequency converter mode |
| Battery | |
| Battery Management | Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units =>continuous maximisation of backup time + deep discharge protection |
| Half Load Runtime (in mins) | 17 |
| Full Load Runtime (in mins) | 12 |
| Communications | |
| User Interface | (3) LEDs + adjustable multilingual display: display of measurements, access to control and setup menus |
| Communication Ports | 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 serial ports cannot be used simultaneously) 1 mini terminal block for remote ON/OFF and emergency stop |
| Communications Card Slots | 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial |
| Environmental & Standards | |
| Audible Noise | 45 dBA |
| Operating Temperature | 0°C to 40°C continuous |
| Performance – Safety – EMC | IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class |
| Approvals | CE, TüV, CB Report, UL |
Selecting the Right UPS
Eaton's power management solutions are based on protecting the nine most common power problems present in any environment. This unique approach makes your product selection decisions about power protection much simpler. The nine power problems listed below are potentially harmful to both your data and your hardware. Eaton's products offer three levels of power protection:
Series 3, Series 5 and Series 9. Based on the parameters defined by your application, you can select an uninterruptible power system (UPS) from the series that best matches your power protection needs.
To provide maximum power protection, Eaton offers a full line of Series 9 UPSs with both single-phase and three-phase models in the Series 9 family.
Within each Series, Eaton has created 3 classes of products; to provide "Good, Better and Best" levels of features and performance and enable the best product fit for any application and budget.

Series 3 Standby UPS: Backup power
| The Eaton's series 3 UPS primarily protects against three of the nine power problems including power failures, power sags and power surges. This essential, cost-effective protection is necessary in order to prevent damage such as data loss, file corruption, hardware damage and equipment shutoff. For example, if your utility fails you could lose all of your work-in-progress. The Series 3 UPS offers a degree of protection against the remaining power problems and is most commonly used to protect single workstations and point-of-sale (POS) equipment. | ![]() |

Series 5 Line Interactive UPS: Keeping it smooth
| Eaton's series 5 UPS are most effective against five power problems (power failures, power sags, power surges, under-voltage and over-voltage) and offer a degree of protection against other power problems. Some of the damages you risk by not using a Series 5 UPS include premature hardware failure, data loss and corruption, data error, keyboard lockup, storage loss and system lockup. Series 5 UPSs are recommended for small network systems – all the way up to enterprise networking environments. | ![]() |

Series 9 On Line Double Conversion UPS: Total Protection
| Eaton's series 9 UPSs protect against all nine power problems: power failures. power sags, power surges, under-voltage, over-voltage, line noise, frequency variation, switching transients and harmonic distortion. Eaton's series 9 comprehensive protection minimises the opportunity for component stress, burnt circuit boards, data crashes and program failures. Series 9 UPSs offer the highest level of power protection available and are always recommended for mission-critical applications like server farms, hospitals and Voice Over Internet Protocol (VOIP) applications. | ![]() |

IEC-320-C20
(8) IEC-320-C13,
(1) IEC-320-C19